1. Research with PCA/ILAC  accreditation

No.

Subject of research / product

 

Type of activity / characteristics examined / method

 

Reference documents

 

1

Windows, doors, roof windows, windows or skylights protruding beyond the face of the partitions.

Heat transfer coefficient
    Calculation method

PN-EN ISO 10077-1:2017 “N”

PN-EN ISO 10077-2:2017 “N”

2

Sections of window frames, doors, their connections to glazing, blinds, roller shutter boxes

Heat transfer coefficient
    Calculation method

 

 

PN-EN ISO 10077-2:2017

PN-EN ISO 10211:2017

3

Curtain walls

Heat transfer coefficient
    Calculation method

PN-EN ISO 12631:2017

PN-EN ISO 6946:2017

PN-EN ISO 10211:2017

4

Glazing

 

Heat transfer coefficient
    Calculation method

PN-EN 673:2011 “N”

5

Windows, doors
Object dimensions up to 1.50 m x 1.50 m

 

Heat transfer coefficient
    Hot box method
    Range U from 0,15 W/(m2k) to 3 W/(m2k)

PN-EN ISO 12567-1:2010+AC:2010

PN-EN ISO 8990:1998

6

Roof windows and other windows protruding from the plane
Object dimensions up to 1.50 mx1.50 m

Heat transfer coefficient
    Hot box method
    Range U from 0,15 W/(m2k) to 3 W/(m2k)

PN-EN ISO 12567-2:2006 “N”

PN-EN ISO 8990:1998

7

Frames
Object dimensions up to 1.50 mx1.50 m

Heat transfer coefficient
    Hot box method
    Range U from 0,15 W/(m2k) to 3 W/(m2k)

PN-EN ISO 12412-2:2005

PN-EN ISO 8990:1998

8

Roller shutter boxes
Object dimensions up to 1.50 mx1.50 m

Heat transfer coefficient
    Hot box method
    Range U from 0,15 W/(m2k) to 4 W/(m2k)

PN-EN ISO 12412-4:2005

PN-EN ISO 8990:1998

9

 

Terminal  ventilation devices. Regulating and closing dampers

 

Tightness of dampers
    Pressure and flow characteristics.

    Range of air leakage volume: from 0.18 m3/h do 1100 m3/h

PN-EN  1751 :2014

 

Testing of a mechanical characteristic of regulating and closing dumpers

Torque measurements of dumpers actuator

Range: from 0,2 Nm to 20 Nm

PN-EN 1751:2014

PN-EN 13053:2020

Aerodynamic characteristics of the regulating and closing dampers.

Pressure and flow characteristics.

Range: from 1 m3/h to 18000 m3/h

PN-EN 1751:2014

PN-EN 13053:2020

10

Ventilation of buildings. Ventilation ducts made of sheet metal with a rectangular cross-section.

 

Duct tightness

    Pressure and flow characteristics.

    Range of air leakage volume: from 0.18 m3/h do 1100 m3/h

PN-EN 1507 :2007

 

11

Ventilation of buildings. Ventilation ducts made of sheet metal with a circular cross-section.

 

Duct tightness
    Pressure and flow characteristics.

    Range of air leakage volume: from 0.18 m3/h do 1100 m3/h

PN-EN 12237 :2005

 

12

Ventilation of buildings. Ductwork. Non-metallic ductwork

 

Air permeability.

    Pressure and flow characteristics.

    Range of air leakage volume: from 0.18 m3/h do 1100 m3/h

PN-EN 17192:2019

13

Ventilation of buildings. Ductwork. Non-metallic ductwork

Pressure drop

Pressure and flow characteristics

Range: from 1 m3/h to 18000 m3/h

PN-EN 17192:2019

14

Windows and doors

 

Air permeability.

    Pressure and flow characteristics.

    Range of air leakage volume: from 0.18 m3/h do 1100 m3/h

PN-EN 1026 : 2016  “N”

PN-EN 12207 :2001

15

 

Ventilation of buildings. Air handling and ventilation units.

 

 

Mechanical strength of the housing
    Range: up to 3000 Pa

PN-EN 1886:2008

The tightness of the housing

   Air leakage flow measurement.

   Range of air leakage volume: from 0.18 m3/h do 1100 m3/h

PN-EN 1886:2008

PN-EN 13053: 2020

Tightness of filter installation

   Air leakage flow measurement.

   Range of air leakage volume: from 0.18 m3/h do 1100 m3/h

PN-EN 1886:2008

PN-EN 13053:2020

Thermal properties of the housing

     Range U from 0,15 W/(m2K) to 6 W/(m2K)

PN-EN 1886:2008

Acoustic insulation of the housing

   Range Dp from 5.0 dB to 70.0 dB

PN-EN 1886:2008

Mechanical safety

PN-EN 1886:2008

Aerodynamic characteristics of the air handling unit
   Range of air volume of air handling unit: from 200
m3/h to 18000 m3/h

PN-EN 13053:2020

Heat recovery section / heat recovery efficiency

    Range of air volume of heat recovery section: from 200 m3/h to 3000 m3/h

PN-EN 13053:2020

Determination of the average air speed class in the housing

    Range of air volume of air handling unit: from 200 m3/h to 18000 m3/h

PN-EN 13053:2020

Housing fan drive power
    Range of air volume of air handling unit: from 200
m3/h to 18000 m3/h

PN-EN 13053:2020

16

Air terminal devises

Lover grilles

Aerodynamic characteristics of  the air terminal devises

Range of air volume::
rom  200 m3/h to 18000 m3/h

PN-EN 13030:2002

Penetration of rainwater

Range of air volume::
rom  200 m3/h to 18000 m3/h

PN-EN 13030:2002

17

Straight ducts and rectangular ventilation fittings

 

Dimensions

Dimension Range:

from 10 mm to 5000 mm

PN-EN 1505:2001

18

Straight ducts and circular ventilation fittings

Dimensions

Dimension Range:

from 10 mm to 5000 mm

PN-EN 1506:2007

19

Glazing

Light and solar properties

Calculation method

 

PN-EN 410-2011  „N”             

20

Non-metallic ventilation ducts

Thermal resistance

Calculation method

Test Procedure PB12 edition 1 of January 13, 2023

 

"N" - Test method used in activities relevant for notification according to the Regulation of the European Parliament and of the Council (EU) No. 305/2011 of March 9, 2011.

 

 

Type of business:

Reference document::

Assessment of performance on the basis of tests and calculations

(System 3)

EU Notified body No. NB 2919

Regulations of the European Parliament and of the Council (EU)

305/2011 of 9 March 2011 laying down harmonized conditions for the marketing of construction products and repealing Council Directive 89/106 / EEC

(Journal of Laws UE L 88 of 04/04/2011, as amended)

 

Commission decision number

Product (s)

Harmonized technical specifications

99/93/WE

Doors, windows

PN-EN 14351-1+A2:2016-10

 

 

 

 

2. Testing as part of a notification issued by TÜV Rheinland for applying for a TÜV certificate

 

No.

Subject of research / product

 

Type of activity / characteristics examined / method

 

Reference documents

 

1

Ventilation of buildings. Air handling and ventilation units. Mechanical properties

Mechanical strength of the housing
    Range: up to 3000 Pa

 

The tightness of the housing

        Pressure and flow characteristics.

        Range of air leakage volume: from 0.18 m3/h do 1100 m3/h

Tightness of filter installation

     Pressure and flow characteristics.

     Range of air leakage volume: from 0.18 m3/h do 1100 m3/h

Thermal properties of the housing

     Range U from 0,15 W/(m2K) to 6 W/(m2K) 

Acoustic insulation of the housing

    Range Dp from 5.0 dB to 70.0 dB

 

Mechanical safety

 

PN-EN 1886 :2008

 

2

Ventilation of buildings. Air handling and ventilation units. Classification and performance characteristics of devices, components and sections

 

 

Aerodynamic characteristics of the air handling unit
    Range of air volume of air handling unit: from 200
m3/h to 18000 m3/h

 

The tightness of the housing

     Pressure and flow characteristics.

     Range of air leakage volume: from 0.18 m3/h do 1100 m3/h

Testing of heat recovery section

    Range of air volume of heat recovery section: from 200 m3/h to 18000 m3/h

 

Determination of the average air speed class in the housing

    Range of air volume of air handling unit: from 200 m3/h to 18000 m3/h

 

Determination of the drive power class of the fan in the control panel
    Range of air volume of air handling unit: from 200
m3/h to 18000 m3/h

 

Tightness of regulating and closing dampers

    Pressure and flow characteristics.

    Range of air leakage volume: from 0.18 m3/h do 1100 m3/h

Tightness of filter installation

    Pressure and flow characteristics.

    Range of air leakage volume: from 0.18 m3/h do 1100 m3/h

PN-EN 13053: 2020

 

3. Research outside of PCA accreditation

 

No,

Subject of research / product

 

Type of activity / characteristics examined / method

 

Reference documents

 

1

Ventilation for buildings. End elements. Supply air grates, diffusers, intake and outlet  shutters

 

Aerodynamic pressure and effective speed calibration in the field of airflow applications

Aerodynamic calibration of the isothermal characteristic of the stream of supply air from the terminal element in the field of applications of the air flow stream

PN-EN 12238 :2002

2

Ventilation for buildings. Performance testing of components/ products for residential ventilation. Cowls and roof outlet terminal devises.

Aerodynamic characteristics - pressure drop, suction action, wind influence test.

Additional test of the devises with fan assistance - aerodynamic performance testing, power consumption test.

PN-EN 13141-5 :2006

3

Ventilation for buildings – Air terminal units – Aerodynamic testing and rating of constant and variable terminal units (VAV, CAV regulators)

Aerodynamic characteristics of the air terminal unit
   Range of air volume of air handling unit: from 1 m3/h to 18000 m3/h

PN-EN 12589:2002

PN-EN 1751:2014

4

Ventilation for buildings – Air terminal units – Aerodynamic testing and rating of constant and variable terminal units (VAV, CAV regulators)

The tightness of the housing

        Pressure and flow characteristics.

        Range of air leakage volume: from 0.18 m3/h do 1100 m3/h

PN-EN 12589:2002

PN-EN 1751:2014

5

Ventilation for buildings – Air terminal units – Aerodynamic testing and rating of constant and variable terminal units (VAV, CAV regulators)

Tightness of closed dampers

    Pressure and flow characteristics.

    Range of air leakage volume: from 0.18 m3/h do 1100 m3/h

PN-EN 12589:2002

PN-EN 1751:2014

V201219E